ACSR  wire is manufactured  with high tensile strength  and high zinc coated solid or stranded  wires as the high  galvanized steel core  for mechanical reinforcement  in aluminium conductors  which are used in  overhead power transmission .

The wire rod should comply with EN 10016-2 and they are manufactured in accordance with EN 50189, EN50183-2000 and BS 4565 standards.

Zinc coating complies with ASTM B 498   standard.

Nominal

Diameter

mm

Dia. Tolerance*

mm
(+/-)

Mass of Zinc

Coating   gr/m²

Tensile

strength

min N/mm²

Elongation

after fracture min. %

Stress at 1 % Extension, min, N/mm²

Over

Up to and inclg

1,25

2,25

0,03

150-200

1340

3

1170

2,26

2,75

0,04

185-230

1310

3

1140

2,76

3,00

0,05

210-250

1310

3,5

1130

3,01

3,50

0,06

230-260

1290

3,5

1100

 